Unique Fire Stop Products - UL Systems

Underwriters Laboratories (U.L.) XHJI.R18017 Through-Penetration Firestop Systems (UL website link)

UL XHEZ.GuideInfo - Through-penetration Firestop Systems (UL website link)

The Hourly Fire Resistance Ratings listed are F Ratings. Some of our systems also have T Ratings.

Split Sleeve Systems Bulkhead Plates
Split Sleeve-Concrete 2 Hr UL W-J-3110 Bulkhead Plate-Drywall 1 & 2 Hr UL W-L-3316
Split Sleeve-Concrete 4 Hr UL W-J-3112  
Split Sleeve-Drywall 1& 2 Hr UL W-L-3232 Membrane Penetrator Systems
Split Sleeve-Drywall 3 & 4 Hr UL W-L-3234 Membrane Penetrator-Drywall 1 & 2 Hr UL W-L-3230
Split Sleeve-Vertical Concrete 2 & 3 Hr UL F-A-3019  
  Smooth Endcaps
Smooth Penetrator Systems * Smooth Endcaps-Concrete 2 Hr UL W-J-0012
Smooth Penetrator-Concrete 2 Hr UL W-J-3109 Smooth Endcaps-Drywall 1 & 2 Hr UL W-L-0021
Smooth Penetrator-Drywall 1 & 2 Hr UL W-L-3231  
* These systems are limited to 2 hour rated horizontal installations. Threaded Endcaps
  Threaded Endcaps-Concrete 2, 3, & 4 Hr UL W-J-0013
Threaded Penetrator Systems Threaded Endcaps-Drywall 1, 2, 3, & 4 Hr UL W-L-0022
Threaded Penetrator-Concrete 2 Hr UL W-J-3111  
Threaded Penetrator-Concrete 4 Hr UL W-J-3112 Fill Kit (Putty) MSDS
Threaded Penetrator-Drywall 1 & 2 Hr UL W-L-3233 Fill Kit (Putty) Material Safety Data Sheet
Threaded Penetrator-Drywall 3 & 4 Hr UL W-L-3234  
Threaded Penetrator-Vertical Concrete 2 & 3 Hr UL F-A-3019 Unique "L" Ratings
  Leakage ratings for our Systems: UL W-L-3122d

Our systems come with enough Unique Putty for a minimum 25% and maximum of 48% cable load.

Packing (eliminated for 1 or 2 hr. Systems) Intumescent Fill Material (putty)
Listings with 3-M, Hilti, Rectorseal and Nelsons all require a minimum of 1 inch of mineral wool batt insulation, packed tightly, into both ends of the sleeve and recessed for the amount of sealant to be used. The wool batt acts as a backing for the intumescent sealant that is used to seal both ends of the sleeve. Mineral wool batt insulation is a common fireproof material used to insulate hot water heaters, fireplace inserts, and heating ducts. The best source for this packing material are the local commercial insulators in your area. Most of our distributors stock it as well. Note that some old-timers may call it rock wool. Our vertical and 4 hr. Systems do require this packing. All of our sleeve systems require the use of an intumescent caulk or putty to seal both ends of the sleeve. This material expands in the presence of heat / flame, suppressing the spread of a fire through the sleeve system penetration. The way a sleeve is packed and sealed are directly proportional to the amount of time a system will suppress a fire. For example, a 1 inch thickness of intumescent putty may be sufficient for a 1 or 2 hour rated penetration but a 3 or 4 hour application might require a 2 (or more) inch thickness in the ends of a sleeve system. Several fill material manufacturers have developed, tested, or engineered through penetration systems combining our sleeves and their fill material. All of our systems now have our intumescent putty included with the sleeve.

 

Unique Fire Stop Products UL Classified Systems with other putty: (Click on the links below.)

3M        HILTI        Nelson 

 

icon1 icon2 icon3

themed image

Secondary Header:

First Heading or Title

Septermber 16, 1926

Lorem Ipsum is simply dummy text of the printing and typesetting industry. Lorem Ipsum has been the industry's standard dummy text ever since the 1500s, when an unknown printer took a galley of type and scrambled it to make a type specimen book. It has survived not only five centuries, but also the leap into electronic typesetting, remaining essentially unchanged. It was popularised in the 1960s with the release of Letraset sheets containing Lorem Ipsum passages, and more recently with desktop publishing software