1. Wall Assembly — Min 6 in. (152 mm) thick
reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3)
concrete. Wall may also be constructed of any UL Classified Concrete Blocks*.
See Concrete Blocks (CAZT) category in the
Fire Resistance Directory for names of manufacturers.
2. Firestop System — The firestop system shall
consist of the following:
A. Firestop Device* — Sleeve - Smooth steel
sleeve device incorporating flat washers secured by sliding compression
couplers. Device shall be installed in accordance with the accompanying
installation instructions. Device provided in nom 1, 2 and 4 in. (25, 51 and 102
mm) diam sizes. Max diam of opening in wall for 1, 2 and 4 in. (25, 51 and 102
mm) size device is 1-1/4, 2-7/16 and 4‑1/2 in. (32, 62 and 114 mm),
respectively.
UNIQUE FIRE STOP PRODUCTS INC — Smooth Sleeve
B. Firestop Device* — End Cap – End cap
device incorporating an octagonal cover plate with a set screw coupling provided
with an intumescent putty fill. Device provided in nom 1, 2 and 4 in. (25, 51
and 102 mm) diam sizes for use with nom 1, 2 and 4 in. (25, 51 and 102 mm) diam
Smooth Sleeve devices (Item 2A). End cap devices installed on both sides of wall
in accordance with accompanying instructions.
UNIQUE FIRE STOP PRODUCTS INC — Smooth Endcap
*Bearing the UL Classification