Threaded Penetrator
Cable Load Chart/Pricing Installation Pictorial Assembly Instructions Drawings UL Systems
![]() |
The Threaded Penetrator™ is used in new cable
installations in which the hole through the fire wall or floor has
been precut such as core drilled in concrete or masonry. It is
constructed of I M C. These Sleeve Systems can be used
horizontally or vertically. Be sure to drill for the Sleeve
System's Outside Diameter! Systems are available in 1, 2, & 4 inch diameters. Part #'s are: TP-1 for the 1" - TP-2 for the 2" and TP-4 for the 4" Threaded Penetrator. See the Cable Load Chart for specifications. Call the factory to order extra long or extra short systems for special applications. 24 hour turnaround! |
| Threaded Penetrator UL Systems: (NOT Part #s) W-J-3111 for concrete walls rated up to 2 hrs. W-J-3112 for concrete walls rated up to 4 hrs. W-L-3233 for drywalls rated for 1 & 2 hrs. W-L-3234 for drywalls rated for 3 & 4 hrs. F-A-3019 for vertical concrete/floors rated for 2 & 3 hrs. ** MSDS for "Unique" Putty. ** There is a 3 inch section that is not threaded. Some floors (less than 3 inches thick) may require the use of a shim to tighten the coupling fully. |
|
| Qty. | System Contents: |
| 1 | 12" threaded rigid sleeve |
| 2 | large flat washers |
| 2 | threaded couplings |
| 2 | plenum rated bushings |
| 2 | documentation/warning labels |
| 1 | "Unique" putty |
| Fire Stopping by the Numbers for the Threaded Penetrator | |
| 1. | You must know the hourly rating of the barrier. 5/8" fire rated gypsum is rated for 1/2 hr. Cinder blocks are rated at 2 hours. |
| 2. | Select the UL Listing (above) to match or exceed the barrier. Pay attention to cable loads and fill procedure in the Listing. |
| 3. | Go to the CABLE LOAD CHART. Select the proper size Penetrator, based on the allowable % cable load permitted in the Listing. |
| 4. | Seek pre-approval from the Authority Having Jurisdiction (Inspector). Remember, it is approved if he says it is! Download the AHJ REQUEST FORM. |
| 5. | When installing the System, be sure not to exceed the listings limitations. Read the listing. |
| 6. | After installation, fill out the label and take a picture to document the System for future reference. |
| If you follow the steps listed above - you will guarantee AHJ acceptance. | |