Split Sleeve System -  Installation Pictorial

 

System consist of: (2) 12 inch long threaded 1/2 sleeves, (4) slotted washers, (2) slotted couplings, (2) split bushings,   a documentation/warning label, and a package of Unique Putty.

 

sss1.jpg (1908 bytes) A common penetration violation in a sheetrock firewall. A Sleeve will control and direct the expansion of the fire rated intumescent putty. Without a sleeve, this penetration may fail to restore the hourly rating of this wall. 

sss2.jpg (13144 bytes)

After you clean up the hole, slide the bottom half of the threaded sleeve under the cables.

sss3.jpg (18821 bytes)

Slide the top half over the cables, maintaining sleeve polarity, until both halves protrude evenly.

sss4.jpg (20397 bytes)

Work the cables through the slot in the first washer and work the washer down the sleeve, against the wall.

The first washers slot should be positioned at the 6 o clock position.

sss5.jpg (12996 bytes)

Install the second slotted washer, inverting the slots 180 degrees from each other. (12 o clock)

sss6.jpg (24699 bytes)

Work the cables through the slotted coupling (again, maintaining polarity) and screw it down the two threaded sleeve halves and against the washers. Repeat this procedure on the other side of the wall.  Coupling should be hand tightened only.

sss7.jpg (25018 bytes)

Install a min. inch thickness of the supplied intumescent fire stop putty to both ends of the Sleeve System.

See our U.L. Systems page for Systems rated up to 4 hours. Intumescent putty is supplied with the system.

split bush.jpg (11539 bytes)

Install the "split bushing", taking care not to open the bushing any more than is needed to get the cables in.
sss9.jpg (66460 bytes) Install the documentation label provided with the system and photograph your installed system.

NOW, BRING ON THE INSPECTOR!