Smooth Penetrator Installation Pictorial

System consist of: A 12 inch length of EMT, (2) large washers, (2) sliding compression couplings, (2) plenum rated bushings, a pair of documentation labels and a package of intumescent putty.
sp.jpg (11211 bytes) You should use a drill with a level.  This will make your Sleeve System look nice and straight!

sp1.jpg (13579 bytes)

A 6 inch bit extension for your hole bits works very well.  Be wary of what might be in the walls.

You might use one of the washers to mark your hole.  Now drill your perfectly straight hole.

sp3.jpg (11438 bytes)

Adjust the hardware to allow for equal protrusion on both sides of the wall.  Insert the first half of the System in the hole you made. There is no need for any caulk between the sleeve and the wall (behind the washers).  Go to the other side....

sp4.jpg (11308 bytes)

On the other side of the wall, install the washer, sliding compression coupling and bushing. While holding the sleeve firmly in the wall, tighten the set screw on the sliding compression coupling. Now you may use the sleeve system as if it were a roller in the firewall, allowing you to pull cables "un-attended ". This is a real time saver!

sp5.jpg (11293 bytes)

Tear the intumescent putty supplied with the system in half.  You will need to apply an inch thickness to each end.  If you do not have enough putty, you may purchase a "Fill Kit".  It is an 18 cubic inch stick of putty.  Part # FK-1

sp6.jpg (11075 bytes)

When the cables reach their destination, install an inch thickness of the supplied intumescent fire stop putty.  Alpha numerically ID your penetration. Be sure to fill out and apply the labels.   Photograph your System !