Unique Fire Stop Products Threaded Penetrator-Block System

(up to 2 hours)

U.L. System No. W-J-3111   F Rating — 2 Hr   T Rating — 0 Hr

(Guide XHEZ   Through-Penetration Firestop Systems)

1.   Wall Assembly — Min 6 in. thick reinforced lightweight or normal weight (100-150 pcf) concrete. Wall may also be constructed of any UL Classified Concrete Blocks*.

See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers.

2.   Cables — Aggregate cross-sectional area of cables in Threaded Sleeve to be min 8 percent to max 48 percent of the aggregate cross-sectional area of the Threaded Sleeve. Cables to be rigidly supported on both sides of wall assembly. Any combination of the following types and sizes of cables may be used:

A. Max 200 pair No. 24 AWG (or smaller) copper conductor cable with polyvinyl chloride (PVC) jacketing and insulation.

B.   Max 1/C, 750 kcmil power cable with copper conductors and cross-linked polyethylene (XLPE) jacketing.

C. Max 3/C No. 2/0 AWG (or smaller) aluminum or copper conductor service entrance cable with PVC insulation and jacket.

D. Max 3/C No. 8 AWG (or smaller) nonmetallic sheathed (Romex) cable with copper conductors, PVC insulation and jacket.

E.   Max 7/C No. 2/0 AWG (or smaller) multiconductor power and control cables with XLPE or PVC insulation and XLPE or PVC jacket.

F.   Max RG59/U (or smaller) coaxial cable with fluorinated ethylene insulation and jacketing.

G. Max 62.5/48 fiber optic cable with PVC insulation and jacketing.

H. Max 4 pair No. 24 AWG (or smaller) copper conductor category 5 with Hylar insulation and jacket.

3.   Firestop System — The firestop system shall consist of the following:

A. Firestop Device* — Threaded steel sleeve device incorporating flat washers secured by threaded couplers. Device shall be installed around cables in accordance with the accompanying installation instructions. Device provided in nom 1, 2 and 4 in. sizes. Max diam of opening in wall for 1, 2 and 4 in. size devices are 1-1/4, 2-7/16 and 4-1/2 in. respectively.

UNIQUE FIRE STOP PRODUCTS INC — Threaded Sleeve

B.   Fill, Void or Cavity Material* Sealant or Putty — Min 1 in. thickness of fill material applied within the Threaded Sleeve, flush with both ends

UNIQUE FIRE STOP PRODUCTS INC

*Bearing the UL Classification Marking