Unique
Fire Stop Products Split Sleeve- (4-Hr) Sheet Rock System
Through-penetration Firestop Systems
System No. W-L-3234
July 31, 2003
F Ratings — 3 and 4 Hr (See Item 1)
T Rating — 0 Hr

1.
Wall Assembly — The 3 or 4 hr fire-rated gypsum
board/steel stud wall assembly shall be constructed of the materials and in
the manner specified in the individual U400 or V400 Series Wall and
Partition Designs in the UL Fire Resistance Directory and shall include the
following construction features:
A.
Studs — Wall framing shall consist of steel
channel studs. Steel studs to be min 3-5/8 in. wide and spaced 24 in. OC.
B.
Gypsum Board* — Multiple layers of min 1/2 in.
thick gypsum board. The gypsum board type, thickness, number of layers
and orientation shall be as specified in the individual Wall and
Partition Design.
The hourly F Rating of the firestop system is equal to the hourly
fire rating of the wall assembly in which it is installed.
2.
Cables — Aggregate cross-sectional area of cables in
sleeve to be min 8 to max 34 percent of the cross-sectional area of the
sleeve. Cables to be tightly bundled. The annular space shall be min 1/4 in.
to max 1-1/4 in. Cables to be rigidly supported on both surfaces of the wall
assembly. Any combination of the following types and sizes of cables may be
used:
A. Max RG59/U (or smaller) coaxial cable with fluorinated
ethylene insulation and jacketing.
B. Max 62.5/48 fiber optic cable with PVC insulation and
jacket.
C. Max 4 pair No. 24 AWG (or smaller) copper conductor data
cable with PVC insulation and jacketing.
3.
Firestop System — The firestop system shall consist
of the following:
A.
Firestop Device* — Threaded steel sleeve device
incorporating flat washers secured by threaded couplers. Device shall be
installed around cables in accordance with the accompanying installation
instructions. Device provided in nom 1, 2 and 4 in. sizes. Max diam of
opening in wall for 1, 2 and 4 in. size devices are 1-1/4, 2-7/16 and
4-1/2 in. respectively.
UNIQUE FIRE STOP PRODUCTS INC — Threaded Sleeve
A1.
Firestop Device* — (Not Shown) — As an alternate
to the threaded sleeve device in Item 3A, threaded steel sleeve halves
incorporating split nuts and split washers sized to fit the specific
diam of the opening may be used. Device shall be installed around cables
in accordance with the accompanying installation instructions. Device
provided in nom 1, 2 and 4 in. sizes. Max diam of opening in wall for 1,
2 and 4 in. size devices are 1-1/4, 2-7/16 and 4-1/2 in. respectively.
UNIQUE FIRE STOP PRODUCTS INC — Split Sleeve
B.
Packing Material — Min 4 pcf mineral wool batt
insulation packed into opening as a permanent form throughout full
length of firestop device except for recess at each end of the device to
accommodate the required thickness of fill material.
C.
Fill Void or Cavity Materials* - Putty — Min 1
in. thickness of fill material applied within annulus, flush both ends
of firestop device.
UNIQUE FIRE STOP PRODUCTS INC —
*Bearing the UL Classification Mark
|