Unique
Fire Stop Products Split Sleeve- (4-Hr) Block System
Through-penetration Firestop Systems
System No. W-J-3112
August 01, 2003
F Rating — 4 Hr
T Rating — 0 Hr

1.
Wall Assembly — Min 7-5/8 in. thick reinforced
lightweight or normal weight concrete wall. Wall may also be constructed of
any nom 8 in. thick (or thicker) UL Classified Concrete Blocks* with
Classification B-4.
See Concrete Blocks (CAZT) category in the Fire Resistance
Directory for names of manufacturers.
2.
Cables — Aggregate cross-sectional area of cables in
sleeve to be min to 8 max 34 percent of the cross-sectional area of the
sleeve. Cables to be tightly bundled. The annular space shall be min 1/4 in.
to max 1-1/4 in. Cables to be rigidly supported on both surfaces of the wall
assembly. Any combination of the following types and sizes of cables may be
used:
A. Max RG59/U (or smaller) coaxial cable with fluorinated
ethylene insulation and jacketing.
B. Max 62.5/48 fiber optic cable with PVC insulation and
jacket.
C. Max 4 pair No. 24 AWG (or smaller) copper conductor data
cable with PVC insulation and jacketing.
3.
Firestop System — The firestop system shall consist
of the following:
A.
Firestop Device* — Threaded steel sleeve device
incorporating flat washers secured by threaded couplers. Device shall be
installed around cables in accordance with the accompanying installation
instructions. Device provided in nom 1, 2 and 4 in. sizes. Max diam of
opening in wall for 1, 2 and 4 in. size devices are 1-1/4, 2-7/16 and
4-1/2 in. respectively.
UNIQUE FIRE STOP PRODUCTS INC — Threaded Sleeve
A1.
Firestop Device* — (Not Shown) — As an alternate
to the threaded sleeve device in Item 3A, threaded steel sleeve halves
incorporating split nuts and split washers sized to fit the specific
diam of the opening may be used. Device shall be installed around cables
in accordance with the accompanying installation instructions. Device
provided in nom 1, 2 and 4 in. sizes. Max diam of opening in wall for 1,
2 and 4 in. size devices are 1-1/4, 2-7/16 and 4-1/2 in. respectively.
UNIQUE FIRE STOP PRODUCTS INC — Split Sleeve
B.
Packing Material — Min 4 pcf mineral wool batt
insulation firmly-packed into opening as a permanent form through full
length of steel sleeve except for recess at each end of device to
accommodate the required thickness of fill material.
C.
Fill, Void or Cavity Materials* - Putty — Min 1
in. thickness of fill material applied within annulus, flush with both
ends of firestop device.
UNIQUE FIRE STOP PRODUCTS INC —
*Bearing the UL Classification Mark
|